Contact
fix6.png
Home > Product > Refrigerant Gas Leakage Monitoring Sensor
AM4215R-TM Series.png

NDIR Triple Refrigerant Gas Leak Sensor
AM4215R-TM SeriesAM4215R-TM Series

Cubic AM4215R-TM Series is an NDIR triple refrigerant gas sensor for the leak detection of R454A, R454C, and R455A refrigerants, specifically designed for the HVACR industry as a complete refrigerant detection system (RDS).

Leveraging advanced NDIR technology, the AM4215R-TM Series ensures excellent long-term stability and selective detection of refrigerant gases. The sensor offers detection across a wide range from 0 to 100% LFL with a 0.1% LFL resolution. Matrix calibration maintains measurement accuracy throughout the full operating temperature range.  Its fast response enables timely leak identification.

Designed for reliability, the AM4215R-TM Series operates continuously in harsh environments from -40°C to +95°C, featuring IP54 protection and resistance to dust accumulation, oil and salt spray corrosion.  An integrated automatic heating mechanism prevents condensation and frost accumulation, while enabling quick recovery after frost, ensuring stable performance in high-humidity or frequently cycling conditions.

The AM4215R-TM series offers dual relays mitigation functions, which includes LED alarm indicators and self-diagnosis functionality for intelligent safety management. Its compact, optimized design supports both integrated wiring-harness and non-harness configurations for easy installation in outdoor units, compressor compartments, air ducts, or other potential leak points. Certified to UL60335-2-40 (4th edition) and UL60335-2-89 standards, the AM4215R-TM Series is a reliable solution for HVAC&R applications, including air conditioning, residential and commercial heat pumps, industrial cooling, and cold chain systems.

Show More

Features

  • NDIR (Non-dispersive Infrared) technology
  • Triple refrigerant gas detection of R454A, R454C, and R455A.
  • Matrix calibration to ensure accuracy under full working temperature
  • Fast response
  • Automatic heating mechanism for anti-condensation and recovery from frost
  • High temperature resistance supports continuous operation at 95℃
  • IP54 protection level
  • Salt spray corrosion resistance
  • Long lifespan over 15 years
  • UL 60335-2-40 & UL 60335-2-89 certified

Specifications

CO2 Sensor CM1106-C
Principle Non-dispersive infrared (NDIR) technology
Target R454A, R454C, R455A
Measurement range 0~100%LFL
Resolution 0.1%LFL
Accuracy ±2.5%LFL@<25%LFL; 10% of reading@25%~100%LFL
Sampling time 1s
Response time TDTLV30s@25%LFL
Alarm point 15%LFL@R454A&R454C&R455A (Default)
Communication output RS485 + relay + LED indicator
Preheating 15 minutes
Protection level IP54
Lifetime 15 years
Working conditions -40~95C; 10%~95%RH@45C (non-condensing)
Storage conditions -40~85C; 0~95%RH (non-condensing)
Working pressure 60~120kPa
Condensation and frost Anti-condensation, recovery from frost
Power supply 20~30VDC (standard 24V)
18~~30vAC/ 47~63Hz (standard 24V)
Power consumption 14VA
Relay type UL File Number E133481
Relay load 1A 30VDC / 0.3A 125VAC
Show More

You can contact Cubic by telephone or email, or you can submit an online Request for Quotation Form.

For Sales: sales@gassensor.com.cn

For Administration: info@gassensor.com.cn

Required*
Send
CONTACT SALES
This website uses cookies to improve your user experience. By using this site, you consent to the use of cookies. You can find more information in our Privacy Policy.