| CO2 Sensor CM1106-C | |
|---|---|
| Principle | Non-dispersive infrared (NDIR) technology |
| Target gas | R454B/R32/R454C/R290 |
| Measurement range | 0-100%LFL |
| Resolution | 0.01%LFL |
| Alarm value | 10%LFL by default |
| Accuracy | ±2.5%LFL@<25%LFL; ±10%of reading @25%~100%LFL |
| Sampling rate | ≤1s |
| Response time | T40≤30s |
| Output | UARTTTL@5V |
| Lifetime | >15 years |
| Protection level | IP54 |
| Working conditions | -30~94 C; 0~95%RH (non -condensing, sustainable work) |
| Storage conditions | -40~70C; 0~95%RH (non-condensing) |
| Working pressure | 80~120kPa |
| Anti-condensation | Anti-condensing |
| Frost recovery: Frost recovery time | ≤15min |
| Power supply | 5±0.2V DC |
| Average working current | ≤300mA |
| Peak current | ≤550mA |
You can contact Cubic by telephone or email, or you can submit an online Request for Quotation Form.