Contact
fix6.png
Home > Product > Refrigerant Gas Leakage Monitoring Sensor
AM4215R-DM Series.png

NDIR Dual Refrigerant Gas Leak Sensor
AM4215R-DM SeriesAM4215R-DM Series

Cubic AM4215R-DM Series is an NDIR dual refrigerant gas sensor, supporting both R32 and R454B refrigerant gas leak detection, specifically designed for the HVACR industry as a complete refrigerant detection system (RDS).

Built on advanced NDIR technology, the AM4215R-DM Series delivers excellent long-term stability and refrigerant gas selectivity.  It features fast response to ensure timely leak identification. Flexible alarm threshold settings are available for different refrigerants. To ensure accuracy across a wide operating range, AM4215-DM implement matrix calibration to maintain accuracy throughout the full working temperature range.

Designed for high reliability, AM4215R-DM Series supports continuous operation in harsh environments, including temperatures from -40°C to +95°C, and features IP54 protection along with salt spray corrosion resistance. An integrated dynamic heating control mechanism effectively prevents condensation and frost formation and enables fast recovery after frosting, allowing the sensor to operate reliably in high-humidity, low-temperature, or frequently cycling environments.

The AM4215R-DM series offers dual relays mitigation functions, while being complemented by LED alarm indication and self-diagnosis for intelligent mitigation control. The compact, optimized structural design also supports both integrated wiring-harness and non-harness variants to simplify installation, making it suitable for inside outdoor units, air ducts, or other potential leak points.

With both sensor and RDS certification available based on the standards of UL60335-2-40 and UL60335-2-89, the Cubic AM4215R DM series is a reliable, high-performance solution for refrigerant leak detection, combining accuracy, durability, and installer-friendly design for HVAC&R applications, including air conditioning systems, residential and commercial heat pumps, and industrial cooling and cold chain and so on.
Show More

Features

  • NDIR (Non-dispersive Infrared) technology
  • Dual refrigerant gas detection of R32& R454B
  • Matrix calibration to ensure accuracy under full working temperature
  • Fast response
  • Multiple DTLV range available
  • Automatic heating mechanism for anti-condensation and recovery from frost
  • High temperature resistance supports continuous operation at 95℃
  • IP54 protection level
  • Salt spray corrosion resistance
  • Long lifespan over 15 years
  • UL 60335-2-40 & UL 60335-2-89 certified

Specifications

CO2 Sensor CM1106-C
Principle Non-dispersive infrared (NDIR) technology
Target gas R32, R454B
Measurement range 0~100%LFL
Resolution 0.1%LFL
Accuracy 2.5%LFL@<25%LFL; 10%of reading@25%~100%LFL
Sampling time 1s
Response time TDTLV30s@25%LFL
Alarm point 15%LFL@R32&R454B
Communication output RS485 + relay + LED indicator
Preheating 15 minutes
Protection level IP54
Lifetime > 15 years
Working conditions -40~95C; 10%~95%RH@45C (non-condensing)
Storage conditions -40~85C; 0~95%RH (non-condensing)
Working pressure 60~120kPa
Condensation and frost Anti-condensation, recovery from frost
Power supply 20~-30VDC (standard 24V)
18~30VAC / 47~63Hz (standard 24V)
Power consumption: 14VA
Relay load 1A 30VDC / 0.3A125VAC